Title:

Temperature efficiency of heat exchangers in air handling units

Creator:

Michalak, Piotr ; Grygierczyk, Stanisław

Subject:

ventilation ; heat recovery ; rotary heat exchanger ; cross-flow heat exchanger ; temperature efficienc ; PN-EN 308

Description:

In order to reduce ventilation heat loss and improve energy efficiency of low-energy buildings air-handling units (AHUs) with heat recovery are used. The article presents results of surveys performed in a passive building located in Katowice concerning the temperature efficiency of heat and cold recovery of two selected AHUs, with different heat exchangers. For this purpose the measurement data from the Building Management System (BMS) for the period 1.08.2015-31.07.2016 were used. The first unit was equipped with a rotary heat exchanger. Its average annual temperature efficiency of heat recovery was 47.2% annually. The efficiency of cold recovery amounted 52.9% on average for the warm half year. The second unit had a cross-flow exchanger. The average annual temperature efficiency of heat recovery in this device was 80.1%. The efficiency of cold recovery amounted 57.2% on average for the warm half year. Additional remarks concerning the temperature measurement in analysed units were also given.

Place of publishing:

Koszalin

Publisher:

Publishing House of the Koszalin University of Technology

Date:

2019

Type:

artykuł w czasopiśmie

Format:

application/pdf

Language:

eng

Is part of:

Journal of Mechanical and Energy Engineering. Vol.3 (43), nr 3, s. 267-272

Rights:

Biblioteka Politechniki Koszalińskiej

Access rights:

internet

License:

Creative Commons BY 4.0

×

Citation

Citation style: